COVID-19 Cleanroom Suite : Design Review
Supplier Management
- The design included three Cleanroom Suites but only two HVAC units
- The HVAC system's exhaust was into the roof void area and not to the outside atmosphere
- By design, suitable filters on the common Cleanroom extract points had been omitted. [In other words, Cleanroom A extract contamination could contaminate Cleanroom B extract]
Contact ZESfor a Subject Matter Expert in Cleanroom design and HVAC systems
ZES regularly act on behalf of Clients to ensure project requirements are satisfied